Note: This is a low voltage only test; do not try to manually
probe the test points when a high bus voltage is applied to this EVM.
- Tie J2 and J5 to low-side and
high-side COM respectively to prevent false triggering of DESAT.
- Turn on the power supply and
adjust the voltage output to 12V. The power supply can connect to either TP4/TP5
on the EVM or to the Wolfspeed differential board.
- Probe the VCC-GND voltage between
the VCC test via and TP11 with a multimeter. This value must be 5V.
- Probe the high side VDD-COM
voltage by using the VDD2 test point and the COM4 or COM5 test point. Probe the
low side VDD-COM voltage by using the VDD1 test point and the COM1 or COM2 test
point. These values must be 15V.
- Probe the high side VEE-COM
voltage by using the VEE2 test point and the COM4 or COM5 test point. Probe the
low side VEE-COM voltage by using the VEE1 test point and the COM1 or COM2 test
point. These values must be -3V.
- Make sure the 5V green LED, the
HS-BIAS blue LED, and the LS-BIAS blue LED are on. The two red RDY LEDs and the
two red FLT LEDs must be off.