STDA029 March   2026 TPS23521 , UCC28704

 

  1.   1
  2.   Abstract
  3.   Trademarks
  4. 1Introduction
  5. 2Floating Ground Hot-Swap Architecture
  6. 3System Design Considerations
  7. 4Design Guidelines and Component Selection
  8. 5Test Results
  9. 6Conclusion
  10. 7References

Abstract

Artificial intelligence (AI) data centers are driving an unprecedented surge in power demand, exceeding 100kW per rack, requiring a shift from traditional 50V DC power distribution to high-voltage direct current (HVDC) architectures at 800V or ±400V. To overcome protection challenges in these HVDC systems, this paper discusses a floating ground hot-swap architecture using a low-voltage controller configured with a reference connected to the load terminal rather than to the system ground. Experimental validation demonstrates a successful 800V operation with a controlled inrush current and microsecond fault detection, while reducing copper usage by 45% and improving efficiency by 5%.