Table 3-8 collects the efficiencies of the DC/AC at 480VAC and 800VDC when operating as a PFC. The results obtained from the power analyzer are taken from 3kW to 18kW. In most of the operating points, the power efficiency is higher than 98% by reaching a maximum of 98.89%. In this test condition, a higher power than 15kW is achieved because the grid input voltage is increased.
| OUTPUT POWER PFC OPERATION | EFFICIENCY | TOTAL HARMONIC DISTORTION |
|---|---|---|
| 3kW | 97.97% | 7.3% |
| 4.69kW | 98.56% | 6.8% |
| 6.55kW | 98.78% | 5.3% |
| 8.42kW | 98.87% | 4.4% |
| 10.3kW | 98.89% | 3.8% |
| 12.21kW | 98.87% | 3.37% |
| 14.13kW | 98.82% | 3% |
| 16.06kW | 98.75% | 2.74% |
| 18.00kW | 98.66% | 2.5% |
All the data summarized in Table 3-8 are collected and plotted as shown in Figure 3-19 and Figure 3-20. By comparing the converter operating at 400VAC, notice that there is an important efficiency improvement. This is because at parity of input current, the power increases but the losses for the same current input are the same. In Figure 3-20 observe that the DC/AC converter shows a total harmonic distortion lower than 3% when the power is higher than 13kW. This is because the ratio between input and output voltage is closer to nominal.