TIDUFG9A December   2025  – March 2026

 

  1.   1
  2.   Description
  3.   Resources
  4.   Features
  5.   Applications
  6.   6
  7. 1System Description
    1. 1.1 Key System Specifications
  8. 2System Overview
    1. 2.1 Block Diagram
    2. 2.2 Design Considerations
      1. 2.2.1 Switching Pattern of a 3-Level Flying Capacitor Switching Cell
      2. 2.2.2 Power Switching Devices Selection and Cooling Approach
      3. 2.2.3 Boost Inductor Selection
      4. 2.2.4 Flying Capacitor Selection
      5. 2.2.5 Cx Capacitance Selection
      6. 2.2.6 DC-Link Output Capacitance Selection
    3. 2.3 Highlighted Products
      1. 2.3.1 LMG3522R030 - 650V, 30mΩ GaN FET With Integrated Driver
      2. 2.3.2 LMG367xR010 650V 10mΩ GaN FET With Integrated Driver and Protection
      3. 2.3.3 TMDSCNCD28P55X - controlCARD Evaluation Module
        1. 2.3.3.1 Hardware Features
        2. 2.3.3.2 Software Features
      4. 2.3.4 TMCS1126 - Precision 500kHz Hall-Effect Current Sensor With Reinforced Isolation
      5. 2.3.5 UCC33421-Q1 Ultra-Small, 1.5W, 5.0V, 5kVRMS Isolation, DC/DC Module
  9. 3Hardware, Software, Testing Requirements, and Test Results
    1. 3.1 Hardware Requirements
    2. 3.2 Test Setup
      1. 3.2.1 Testing TIDA-010957 Connected to the Grid With DC-Link
    3. 3.3 Test Results
      1. 3.3.1 Testing TIDA-010957 Connected to the Grid With DC-Link Using LMG3522R030: Balanced Currents
        1. 3.3.1.1 Nominal Apparent Power
        2. 3.3.1.2 Efficiency vs Power vs DC-Link Voltage
          1. 3.3.1.2.1 Testing the Converter: 700VDC Input to 400VAC Output
          2. 3.3.1.2.2 Testing the Converter: 800VDC Input to 400VAC Output
          3. 3.3.1.2.3 Testing the Converter: 900VDC Input to 400VAC Output
          4. 3.3.1.2.4 Testing the Converter: 800VDC Input to 480VAC Output
      2. 3.3.2 Testing TIDA-010957 Tied to the Grid With DC-Link Using LMG3522R030: Unbalance Currents
      3. 3.3.3 Testing TIDA-010957 Connected to the Grid With DC-Link Using LMG3670R010: Balanced Currents
  10. 4Design and Documentation Support
    1. 4.1 Design Files
      1. 4.1.1 Schematics
      2. 4.1.2 BOM
    2. 4.2 Documentation Support
    3. 4.3 Support Resources
    4. 4.4 Trademarks
  11. 5About the Author
  12. 6Revision History
Testing the Converter: 800VDC Input to 480VAC Output

Table 3-8 collects the efficiencies of the DC/AC at 480VAC and 800VDC when operating as a PFC. The results obtained from the power analyzer are taken from 3kW to 18kW. In most of the operating points, the power efficiency is higher than 98% by reaching a maximum of 98.89%. In this test condition, a higher power than 15kW is achieved because the grid input voltage is increased.

Table 3-7 DC/AC at 800VDC and 480VAC Working as a PFC
OUTPUT POWER PFC OPERATION EFFICIENCY TOTAL HARMONIC DISTORTION
3kW 97.97% 7.3%
4.69kW 98.56% 6.8%
6.55kW 98.78% 5.3%
8.42kW 98.87% 4.4%
10.3kW 98.89% 3.8%
12.21kW 98.87% 3.37%
14.13kW 98.82% 3%
16.06kW 98.75% 2.74%
18.00kW 98.66% 2.5%

All the data summarized in Table 3-8 are collected and plotted as shown in Figure 3-19 and Figure 3-20. By comparing the converter operating at 400VAC, notice that there is an important efficiency improvement. This is because at parity of input current, the power increases but the losses for the same current input are the same. In Figure 3-20 observe that the DC/AC converter shows a total harmonic distortion lower than 3% when the power is higher than 13kW. This is because the ratio between input and output voltage is closer to nominal.


TIDA-010957 DC/AC Efficiency at 800VDC and
            480VAC

Figure 3-19 DC/AC Efficiency at 800VDC and 480VAC

TIDA-010957 Total Harmonic Distortion for the
            DC/AC at 800VDC and 480VAC

Figure 3-20 Total Harmonic Distortion for the DC/AC at 800VDC and 480VAC