Abnormal Speed [ABN_SPEED]

MCT8316A monitors the speed continuously by calculating difference in time between subsequent back-EMF zero crossings. This fault gets triggered when motor speed exceeds abnormal speed threshold [LOCK_ABN_SPEED]. When the motor gets stuck in the first electrical cycle, device continues to commutate at frequencies above the configured abnormal speed threshold [LOCK_ABN_SPEED].

When this fault gets triggered, follow below recommendations.

  1. Increase align time [ALIGN_TIME].

  2. Decrease slow first cycle frequency [SLOW_FIRST_CYC_FREQ]

  3. Decrease open loop acceleration A1 [OL_ACC_A1] and open loop acceleration A2 [OL_ACC_A2].

  4. Decrease closed loop acceleration [CL_ACC]