Figure 4-3 and Table 4-4 show the overall efficiency converting from DC Bus to 230VAC output. The results are discussed for comparison of all three modulation schemes, H-Bridge in unipolar, H-Bridge in bipolar and HERIC modes.
The table shows that the reference design in H-Bridge Unipolar mode achieves a ηpeak = 98.2% at approximately 2.9kW and 400V input, ηfull-load of 98.0% and ηCEC = 97.9% .
The table shows that the reference design in H-Bridge Bipolar mode achieves a ηpeak = 98.0% at approximately 2.8kW and 400V input, ηfull-load of 97.7% and ηCEC = 97.8%.
The table shows that the reference design in HERIC mode achieves ηpeak = 98.4% at approximately 2.1kW and 400V input, ηfull-load of 98.2% and ηCEC = 98.3%.
| OUTPUT POWER | EFFICIENCY FOR H-BRIDGE UNIPOLAR |
OUTPUT POWER | EFFICIENCY FOR H-BRIDGE BIPOLAR |
OUTPUT POWER | EFFICIENCY FOR HERIC |
|---|---|---|---|---|---|
| 0.3kW | 94.1% | 0.3kW | 95.2% | 0.4kW | 96.6% |
| 0.5kW | 95.6% | 0.5kW | 96.2% | 0.5kW | 97.3% |
| 0.7kW | 96.5% | 0.7kW | 96.8% | 0.7kW | 97.7% |
| 0.9kW | 97.0% | 1.0kW | 97.4% | 0.9kW | 98.0% |
| 1.0kW | 97.2% | 1.4kW | 97.6% | 1.2kW | 98.2% |
| 1.4kW | 97.8% | 1.8kW | 97.8% | 1.4kW | 98.3% |
| 1.8kW | 97.9% | 2.1kW | 97.9% | 1.8kW | 98.4% |
| 2.1kW | 98.0% | 2.3kW | 97.9% | 2.1kW | 98.4% |
| 2.3kW | 98.1% | 2.5kW | 97.9% | 2.3kW | 98.4% |
| 2.5kW | 98.1% | 2.8kW | 98.0% | 2.5kW | 98.4% |
| 2.7kW | 98.1% | 3.2kW | 97.9% | 2.8kW | 98.4% |
| 2.9kW | 98.2% | 3.4kW | 97.9% | 3.0kW | 98.4% |
| 3.0kW | 98.2% | 3.8kW | 97.9% | 3.2kW | 98.4% |
| 3.2kW | 98.2% | 3.9kW | 97.9% | 3.4kW | 98.3% |
|
3.4kW |
98.2% |
4.1kW |
97.8% | 3.6kW | 98.3% |
|
3.6kW |
98.2% |
4.3kW |
97.8% | 3.8kW | 98.3% |
| 3.8kW | 98.1% |
4.4kW |
97.8% | 3.9kW | 98.3% |
| 3.9kW | 98.1% |
4.6kW |
97.7% |
4.1kW |
98.2% |
|
4.1kW |
98.1% |
4.3kW |
98.2% | ||
|
4.3kW |
98.1% |
4.4kW |
98.2% | ||
|
4.4kW |
98.0% |
4.5kW |
98.1% | ||
|
4.6kW |
98.0% |