SLVAG33 August 2026 DRV8904-Q1 , DRV8906-Q1 , DRV8908-Q1 , DRV8910-Q1 , DRV8912-Q1
In the application, it was found that when configuring Low-Current Active OLD (LOLD), even if the load is disconnected from the output terminal, the fault cannot be triggered (nFAULT is not pulled low, and the OLD bit in IC_STAT is not set). After changing to the standard Active OLD configuration, under the same load disconnection condition, the open-circuit state can be correctly detected and the fault reported.
The actual register settings are as follows: HB3_LS_EN = 1b (low-side FET enabled), HB3_OLD_DIS = 1b (OLD function disabled), HB3_LOLD_EN = 1b (LOLD enabled).
Test conditions: VM = 13.5V, a 3135Ω load is connected and then disconnected. Result: nFAULT remains high at all times, and the LOLD fault is not detected (FAIL).