TIDUF03 December 2022
Response time was measured for both AC and DC faulty currents. In Figure 3-17, the TIDA-010237 is sensing a 30 mARMS and resulted in a response time of approximately 18 ms.
Figure 3-17 System Response to
30-mARMS Fault CurrentIn Figure 3-18, the TIDA-010237 is sensing 6 mA and resulted in a response time of approximately 24 ms.
Figure 3-18 System Response to 6-mA Fault
Current