VOUT_UV_WARN is a standard PMBus® command for configuring or reading an 8-bit threshold for the output undervoltage warning detection. This command uses the PMBus® DIRECT format. When reading and writing to this register, use the coefficients shown in Table 7-65, Equation 14, and Equation 15 to convert between the real world units and hexadecimal values.
This command uses the PMBus® read or write word protocol.
Contents of this register are compared to the VOUT ADC telemetry value. If the measured VOUT value falls below the value in this register, the VOUT_UV_WARN flags are set in the respective registers. The SMBA signal is asserted. When the output voltage rises above the VOUT_UV_WARN threshold, and the CLEAR_FAULTS command is sent afterwards, this warning flag and alert clear.
| Bit | Name | Description | Minimum Value | Maximum Value | Default Value | Access |
|---|---|---|---|---|---|---|
15:0 | VOUT_UV_WARN | Output undervoltage warning threshold | 0x0000h (0V) | 0x00FFh (87.75V) | 0x0020h (11V) | Read/Write |
When an output undervoltage warning is detected, the device:
sets the NONE_OF_THE_ABOVE/UNKNOWN bit in the STATUS_BYTE register
sets the OUT_STATUS bit in the upper byte of the STATUS_WORD register
sets the VOUT_OV_WARN bit in the STATUS_OUT register
notifies the host by asserting SMBA, if it is not masked setting the STATUS_OUT bit in the ALERT_MASK register.
A write command to this register must be preceded by the MFR_WRITE_PROTECT command to unlock the device first to prevent accidental or spurious writes.