Signal Levels

RS-485 standard conform drivers provide a differential output of a minimum 1.5 V across a 54-Ω load, whereas standard conform receivers detect a differential input down to 200 mV. The two values provide sufficient margin for a reliable data transmission even under severe signal degradation across the cable and connectors. This robustness is the main reason why RS-485 is well suited for long-distance networking in noisy environment.

GUID-B63E78A2-8611-4260-897B-DD89F8DDDFED-low.gif Figure 4-1 RS-485 Specified Minimum Bus Signal Levels