The TPS1689x responds to output overcurrent conditions during steady-state by performing a circuit-breaker action after a user-programmable transient fault blanking interval. This action allows the device to support a higher peak current for a short user-defined interval but also establishes robust protection in case of persistent output faults.
The device constantly senses the output load current and provides an analog current output (IIMON) on the IMON pin which is proportional to the load current, which in turn produces a proportional voltage (VIMON) across the IMON pin resistor (RIMON) as per Equation 4.
Where GIMON is the current monitor gain (IIMON : IOUT)
The overcurrent condition is detected by comparing this voltage against the voltage on the IREF pin as a reference. The reference voltage (VIREF) can be controlled in two ways, which sets the overcurrent protection threshold (IOCP) accordingly.
The reference voltage (VIREF) can be generated using internal DAC and can be changed by programming the nonvolatile configuration memory or dynamically through PMBus® writes to the VIREF register.
The overcurrent protection threshold during steady-state (IOCP) can be calculated using Equation 5.
TI recommends to add a 1nF capacitor from IREF pin to GND for improved noise immunity.
After an overcurrent condition is detected, that is the load current exceeds the programmed current limit threshold (IOCP), but stays lower than the short-circuit threshold (ISCP), the device starts running the internal overcurrent blanking digital timer (OC_TIMER). If the load current drops below the current limit threshold before the OC_TIMER expires, the circuit-breaker action is not engaged. This action allows short overload transient pulses to pass through the device without tripping the circuit. At the same time, the OC_TIMER is reset so that it is at its default state before the next overcurrent event. This establishes the full blanking timer interval is provided for every overcurrent event.
If the overcurrent condition persists, the OC_TIMER continues to run and after it expires, the circuit-breaker action turns off the FET immediately.
Equation 18 can be used to calculate the RIMON value for the desired overcurrent threshold.
The duration for which transients are allowed can be programmed using OC_TIMER register setting through PMBus® writes.
Figure 7-4 shows the overcurrent response for TPS1689x eFuse. After the part shuts down due to a circuit-breaker fault, it either stays latched off or restarts automatically based on the RETRY_CONFIG register setting.
Figure 7-4 Steady-State Overcurrent (Circuit-Breaker) ResponseWhen a transient overcurrent condition (the load current exceeds the programmed current limit threshold but the OC_TIMER does not expire) is detected, the device:
When a persistent overcurrent condition (the load current exceeds the programmed current limit threshold and the OC_TIMER expires) is detected, the device:
It is assumed that the VIN_UV_WARN and VIN_OV_WARN events are not triggered because of a step load transient.