SNVSCT1 October   2025 LM5066H

ADVANCE INFORMATION  

  1.   1
  2. Features
  3. Applications
  4. Description
  5. Device Comparison Table
  6. Pin Configuration and Functions
  7. Specifications
    1. 6.1 Absolute Maximum Ratings
    2. 6.2 ESD Ratings
    3. 6.3 Recommended Operating Conditions
    4. 6.4 Thermal Information
    5. 6.5 Electrical Characteristics
  8. Detailed Description
    1. 7.1 Overview
    2. 7.2 Functional Block Diagram
    3. 7.3 Feature Description
      1. 7.3.1  Current Limit
      2. 7.3.2  Foldback Current Limit
      3. 7.3.3  Soft Start Disconnect (SFT_STRT)
      4. 7.3.4  Circuit Breaker
      5. 7.3.5  Power Limit
      6. 7.3.6  UVLO
      7. 7.3.7  OVLO
      8. 7.3.8  Power Good
      9. 7.3.9  VDD Sub-Regulator
      10. 7.3.10 Remote Temperature Sensing
      11. 7.3.11 Damaged MOSFET Detection
      12. 7.3.12 Analog Current Monitor (IMON)
    4. 7.4 Device Functional Modes
      1. 7.4.1 Power Up Sequence
      2. 7.4.2 Gate Control
      3. 7.4.3 Fault Timer and Restart
      4. 7.4.4 Shutdown Control
      5. 7.4.5 Enabling/Disabling and Resetting
    5. 7.5 Programming
      1. 7.5.1 PMBus Command Support
  9. Application and Implementation
    1. 8.1 Application Information
    2. 8.2 Typical Application
      1. 8.2.1 54V, 100A PMBus Hot Swap Design
        1. 8.2.1.1 Design Requirements
        2. 8.2.1.2 Detailed Design-In Procedure
          1. 8.2.1.2.1 Selecting the Hotswap FETs
          2. 8.2.1.2.2 dv/dt-Based Start-Up
            1. 8.2.1.2.2.1 Choosing the VOUT Slew Rate
          3. 8.2.1.2.3 Select RSNS and CL Setting
          4. 8.2.1.2.4 Select Power Limit
          5. 8.2.1.2.5 Set Fault Timer
          6. 8.2.1.2.6 Check MOSFET SOA
          7. 8.2.1.2.7 Set UVLO and OVLO Thresholds
            1. 8.2.1.2.7.1 Option A
            2. 8.2.1.2.7.2 Option B
            3. 8.2.1.2.7.3 Option C
            4. 8.2.1.2.7.4 Option D
          8. 8.2.1.2.8 Power Good Pin
          9. 8.2.1.2.9 Input and Output Protection
        3. 8.2.1.3 Application Curves
    3. 8.3 Power Supply Recommendations
    4. 8.4 Layout
      1. 8.4.1 Layout Guidelines
      2. 8.4.2 Layout Example
  10. Device and Documentation Support
    1. 9.1 Third-Party Products Disclaimer
    2. 9.2 Receiving Notification of Documentation Updates
    3. 9.3 Support Resources
    4. 9.4 Trademarks
    5. 9.5 Electrostatic Discharge Caution
    6. 9.6 Glossary
  11. 10Revision History
  12. 11Mechanical, Packaging, and Orderable Information
    1. 11.1 Package Option Addendum
    2. 11.2 Tape and Reel Information
    3. 11.3 Mechanical Data

Refer to the PDF data sheet for device specific package drawings

Mechanical Data (Package|Pins)
  • PWP|28
Thermal pad, mechanical data (Package|Pins)

Current Limit

The LM5066Hx provides current limit protection with eight programmable thresholds ranging from 10 mV to 50 mV. Current limiting activates when the voltage across the sense resistor RSNS (between VIN_K and SENSE pins) exceeds the selected threshold. Two thresholds can be set directly using the CL pin, 25 mV when CL is connected to VDD and 50 mV when CL is connected to GND. The remaining six thresholds are available by programming the DEVICE_SETUP1 and DEVICE_SETUP2 registers through the PMBus interface.

During an over current event, the device offers two protection modes: over current blanking and current limiting. These modes can operate independently or sequentially based on configuration.

In over current blanking mode, the device allows the load current to flow without limiting it for a set time period, as long as it remains below the circuit breaker threshold (VCB). The LM5066Hx features two over current blanking thresholds with separate timers:

  • VCBL1 with timer tCBL1 for moderate over currents

  • VCBL2 with timer tCBL2 for higher over currents

These thresholds and timers are configured in the DEVICE_SETUP3 and OC_BLANKING_TIMERS registers. Typically, VCBL1 is set higher than VCL, and VCBL2 is set higher than VCBL1. For load currents between VCL and VCBL2, the tCBL1 timer activates. For load currents between VCBL1 and VCBL2, the tCBL2 timer activates.

The timer resets if the current drops below the respective threshold before it expires. If either timer expires due to prolonged overload, the device transitions to current limiting mode. In the LM5066H2, GATE2 turns off immediately when either timer expires. Over current blanking mode can be disabled by setting tCBL1 and tCBL2 to 0 μs.

In current limiting mode, the GATE voltage is regulated such that the current through MOSFET driven by GATE1 is limited to the set current limit threshold. The fault timer activates during current limiting. If the load current falls below the current limit threshold before the fault timer expires, normal operation resumes. If the current limit persists beyond the fault timeout period set by CTMR, GATE1 turns off. Current limiting can be disabled by setting bit 7 in DEVICE_SETUP3. When disabled, both GATE1 and GATE2 turn off after the blanking phase when either of the blanking timer expires. When a current limit fault occurs, the device sets fault flags in the STATUS_INPUT (7Ch), STATUS_WORD (79h), and DIAGNOSTIC_WORD (E1h) registers, and asserts the SMBA pin. SMBA signaling can be disabled using the ALERT_MASK (D8h) register.For reliable operation, the RSNS resistor value should not exceed 200 mΩ to avoid instability in the current limit control loop.

LM5066H Current Limit, Blanking and Circuit Breaker ThresholdsFigure 7-1 Current Limit, Blanking and Circuit Breaker Thresholds
Table 7-1 Current Limit, Foldback Current Limit, Over Current Blanking, Circuit Breaker and Other Threshold Settings
ParameterNo. of Configurable ThresholdsThresholds Values

Analog / Digital

Over Current Limit Threshold, VCL8

10mV, 12.5mV, 15mV,17.5mV, 20mV, 22.5mV and 25mV, 50mV

Analog
Over Current Blanking1 Threshold, VCBL141.25xVCL, 1.5xVCL, 1.75xVC, 2xVCLAnalog
Over Current Blanking2 Threshold, VCBL241.5xVCL, 1.75xVCL, 2xVCL, 2.25xVCLAnalog
Circuit Breaker Threshold, VCB41.2xVCL, 2xVCL, 3xVCL,4xVCLAnalog
Short Circuit Protection Threshold, VSCP11.5xVCBAnalog
Foldback Factor during StartUp30.05xVCL, 0.1xVCLAnalog
Over Current Blanking Timer1160ms - 100msDigital
Over Current Blanking Timer2160ms -10ms, 100msDigital
Circuit Breaker Blanking Time1100usAnalog

Regulation Timer

(Constant Current Timer / P2t Timer)

Set with TIMER pinConfigurable using CTIMERAnalog
P2t Timer - Insertion Timer410ms – 100msDigital
P2t Timer - Retry Timer1610ms – 10sDigital
Watch Dog Timer during Startup/Retry1610ms – 10sDigital