The design requirements are:
- Transmitter with a current output
range of 4mA to 20mA to represent a process variable signal
- Out-of-range current output capability less than 3.6mA and
greater than 21mA for NAMUR NE43 sensor-fault signal levels
- Total onboard current less than or equal to 3mA to operate
the board, but allow for low out-of-range outputs
- Operation with standard
industrial automation supply voltages from 15V to 36V
- Current and voltage outputs with
TUE less than 0.5% at 25°C after calibration