SLVSGS5A December 2023 – June 2024 DRV3946-Q1
PRODUCTION DATA
Let us assume -
Total 8 loads connected to four DRV3946-Q1 devices, with all loads energized together
Load: L = 400 mH, R = 4 Ω
Peak current IPC = 1 A, Hold current IHC = 0.5 A
HS switch is shut off
PVDD UV threshold = 5 V
PVDD voltage clamp limit = - 1V
OUTx LS passive clamp = 29 V
With these assumptions, we can derive the following -
Voltage across load during clamp VCLAMP= 29 – (-1) V = 30 V
Clamping duration tCLAMP = I x L / VCLAMP
For peak current, clamping duration tCLAMP = 1 A x 0.4 H / 30 V = 13.3 ms
For hold current, clamping duration tCLAMP = 0.5 A x 0.4 H / 30 V = 6.67 ms
Charge sourced from PVDD cap (QPVDD) = I X tCLAMP / 2
For peak current, charge sourced from PVDD cap = 1 A x 13.3 ms / 2 = 6.67 mC
For hold, charge sourced from PVDD cap = 0.5 A x 6.67 ms / 2 = 1.67 mC
Allowed delta voltage on PVDD cap = PVDD UV threshold – PVDD voltage clamp limit = 5 – (-1) = 6 V
Cap on PVDD = N x QPVDD / ΔV
For peak , cap on PVDD = 8 x 6.67 mC / 6 V = 8.9 mF
For hold, cap on PVDD = 8 x 1.67 mC / 6 V = 2.2 mF
In this case, using a diode parallel to the PVDD cap of ~47 μF is more practical than a large capacitor. Diode current capability and thermal constraints should be considered. Alternate solution would be to replace the HS switch and the diode with a half-bridge driver device.