SLVSHO1 March 2025 TPS1689
ADVANCE INFORMATION
This design example considers a 54V system operating voltage with a tolerance of ±10%. The maximum steady-state load current is 40A. If the load current exceeds 44A, the eFuse circuit must allow transient overload currents up to a 4 ms interval. For persistent overloads lasting longer than that, the eFuse circuit must break the circuit and then latch-off. The eFuse circuit must charge a bulk capacitance of 2mF .Figure 7-5 shows the application schematic for this design example.