SNAS264D April 2006 – February 2024 LM94
PRODUCTION DATA
| Register Address |
Read/ Write |
Register Name |
Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 | Default Value |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 80h | R/W | Fan Boost Temp Zone 1 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | 3Ch |
| 81h | R/W | Fan Boost Temp Zone 2 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | 3Ch |
| 82h | R/W | Fan Boost Temp Zone 3 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | 23h |
| 83h | R/W | Fan Boost Temp Zone 4 |
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | 23h |
If any thermal zone exceeds the temperature set in the Fan Boost Limit register, both of the PWM outputs are set to 100%. The fan boost function takes precedence over low-resolution manual override. High-resolution manual overide takes priority over the fan boost function. This is a safety feature that attempts to cool the system if there is a potentially catastrophic thermal event. If set to 7Fh and the fan control temperature resolution is 1°C, the feature is disabled.
Default = 60°C = 3Ch for zones 1 and 2
Default = 35°C = 23h for zones 3 and 4
The temperature has to fall the number of degrees specified in the Fan Boost Hysteresis registers, below this temperature to cause the PWM outputs to return to normal operation. The fan boost function can be disabled by setting the associated register to 80h.